TK7460
Temperature switch with intuitive switch point setting
TK-250CLFR12-QKPKG / US
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen — We reserve the right to make technical alterations without prior notice. — EN-GB — TK7460-00 — 24.08.2016 —
Outputs
Total number of outputs
2
Output signal
switching signal
Electrical design
PNP
Number of digital outputs
2
Output function
normally open / normally closed
Max. voltage drop switching
output DC
[V]
2
Permanent current rating of
switching output DC
[mA]
500
Short-circuit protection
yes
Type of short-circuit
protection
pulsed
Overload protection
yes
Measuring/setting range
Measuring range -25...140 °C -13...284 °F
Set point SP -20...140 °C -4...284 °F
Accuracy / deviations
Temperature drift per 10 K [K]
0.1 **)
Repeatability [K]
± 0,1
Setting accuracy [K]
± 3
Response times
Dynamic response T05 / T09 [s]
1 / 3; (to DIN EN 60751)
Software / programming
Adjustment of the switch
point
setting rings
Operating conditions
Ambient temperature [°C]
-40...80
Note on ambient temperature
at medium temperature: < 80 °C
-40...50 °C
at medium temperature: < 145 °C
Storage temperature [°C]
-40...100
Protection
IP 67
Tests / approvals
EMC
DIN EN 61000-4-2 ESD 4 kV CD / 8 kV AD
EN 61000-4-3 HF radiated 10 V/m
DIN EN 61000-4-4 Burst 2 kV
EN 61000-4-6 HF conducted 10 V
Shock resistance DIN IEC 68-2-27 50 g (11 ms)
Vibration resistance DIN EN 60068-2-6 20 g (10...2000 Hz)
MTTF [years]
643.1
UL approval UL Approval no. K018